What is the capacity factor of solar? The solar capacity factor is the energy that a solar plant produces in a period divided by what it would produce at full rated power in every hour. Published averages range from about 11% in Germany and the United Kingdom to 24% in the United States, measured on the AC rating. Plants completed worldwide in 2025 average 16.5% on the DC rating.
A solar plant produces nothing at night and little under clouds, so its production over a year is a fraction of what its rated power would allow. The capacity factor measures that fraction. For solar it comes with a trap that other technologies do not have: a solar plant has two ratings, and each gives a different capacity factor. This article gives the formula, compares markets, and shows how to tell which figure you are looking at.
Solar capacity factor: formula and example
Capacity factor = energy produced ÷ (capacity × hours in the period)
300,000 MWh ÷ (120 MW × 8,760 h) = 28.5%
The example plant has an AC rating of 120 MW and produces 300,000 MWh in a year of 8,760 hours. At full output in every hour it would produce 1,051,200 MWh. It reaches 28.5% of that ceiling. The same result can be stated in full load hours: 300,000 MWh ÷ 120 MW = 2,500 hours.
DC vs AC: two capacity factors for one solar plant
A solar plant carries two ratings. The DC rating is the capacity of its modules, in megawatt-peak (MWp). The AC rating is what its inverters can deliver to the grid, in MWac. In the United States the module capacity of utility-scale plants is about 1.3 times the inverter capacity on average, according to Berkeley Lab.
The example plant has 150 MWp of modules behind its 120 MWac. The same 300,000 MWh give two results.
| 300,000 MWh a year | On the DC rating (150 MWp) | On the AC rating (120 MWac) |
|---|---|---|
| Ceiling at full output all year | 1,314,000 MWh | 1,051,200 MWh |
| Full load hours | 2,000 h, the specific yield | 2,500 h |
| Capacity factor | 22.8% | 28.5% |
Neither figure is wrong. The two differ by the DC/AC ratio of the plant, here 150 ÷ 120 = 1.25. The capacity factor on the DC rating is the specific yield of the plant divided by 8,760 hours, as the article on energy yield explains.
Capacity factor (AC) = capacity factor (DC) × DC/AC ratio
22.8% × 1.25 = 28.5%
Enter the two ratings and the production of a plant to get all of its figures:
Calculator
Specific yield and capacity factor of a solar plant
Specific yield: 2,000 kWh/kWp
Capacity factor on the DC rating: 22.8% · on the AC rating: 28.5%
Full load hours on the AC rating: 2,500 h · DC/AC ratio: 1.25
Specific yield = production ÷ DC capacity. Capacity factor = production ÷ (capacity × 8,760 hours). The figure on the AC rating is higher than the one on the DC rating by the DC/AC ratio.
Free PDF · The RVA Body of Knowledge
The complete curriculum of renewable energy project finance
42 readings in five topic areas, from power and energy to debt sizing and battery storage, with practice questions after every reading. The Complete Edition is free.
Typical solar capacity factors by country
The table compares published averages. Note the rating behind each figure.
| Market | Solar capacity factor | Basis and source |
|---|---|---|
| Germany | 11.0% | Average of 2015 to 2025, about 960 full load hours a year (Fraunhofer ISE) |
| United Kingdom | 11.1% | Load factor for 2025 (Department for Energy Security and Net Zero) |
| World, new plants | 16.5% | Plants completed in 2025, on the DC rating (International Renewable Energy Agency) |
| United States | 24.0% | All utility-scale plants in 2025, on the AC rating (U.S. Energy Information Administration) |
Two things explain the spread. The first is the site: the United States has far sunnier regions than Germany or the United Kingdom. The second is the rating. The worldwide 16.5% is on the DC rating and the 24.0% of the United States on the AC rating, so part of that gap has nothing to do with sunshine.
The range within one country is wide as well. Berkeley Lab reports regional averages for utility-scale plants in the United States from 16% in the least sunny regions to 33% in the sunniest, all on the AC rating.
What drives the capacity factor of a solar plant
- Sunshine at the site. More solar irradiation over the year means more production from every installed megawatt. No design choice replaces a sunny site.
- Trackers. Modules on trackers follow the sun through the day. In the United States they reach about five percentage points more than fixed modules, on the AC rating (Berkeley Lab).
- The DC/AC ratio. More module capacity behind the same inverters raises the capacity factor on the AC rating. In the sunniest hours the inverters cut off what exceeds their rating, so the figure on the DC rating falls slightly.
- Losses inside the plant. Shading, dirt on the modules, heat and electrical losses separate the gross yield from the net yield.
- Age and operation. The output of modules declines slowly over the years, which is called degradation. Downtime and curtailment lower the production of a given year.
A solar plant also produces far more in the summer months than in the winter months. The capacity factor of a single month or quarter therefore says little about the year. Compare full years, and see how to model the seasonality of production for monthly and quarterly models.
How to check a quoted solar capacity factor
Four questions sort out most figures.
| Question | A sound figure states | A warning sign |
|---|---|---|
| Which site? | A location you can compare with published averages | A figure far above its region, with no explanation |
| Which rating? | DC or AC | A solar capacity factor with no rating |
| Which period? | A full year with all capacity in service | A good month or quarter presented as the year |
| Which stage? | Gross, net P50 or sold; forecast or achieved | A gross yield used as if it were energy sold |
Take a teaser for a plant on trackers in southern Spain: 100 MWp / 80 MWac, 195 GWh a year (P50), capacity factor 27.8%. The production gives 195,000 MWh ÷ 100 MWp = 1,950 kWh/kWp, or 22.3% on the DC rating. Times the DC/AC ratio of 1.25, that is 27.8%. The teaser quotes the figure on the AC rating without saying so.
Common mistake: comparing a DC figure with an AC figure. A capacity factor of 22.3% on the DC rating and one of 27.8% on the AC rating can describe the same plant. Put both figures on the same rating before you compare two solar plants.
Key takeaways: solar capacity factor
- Solar capacity factor = energy produced ÷ (capacity × hours in the period).
- Every solar plant has two capacity factors, one on the DC rating of its modules and one on the AC rating of its inverters. They differ by the DC/AC ratio.
- Published averages run from about 11% in Germany and the United Kingdom to 24% in the United States (AC rating). New plants worldwide average 16.5% on the DC rating.
- The site comes first, then trackers, the DC/AC ratio and the losses inside the plant.
- A figure needs four labels: the site, the rating, the period and the stage.
Practice questions
Three questions in the format of the RVA Body of Knowledge. Pick an answer to check it.
1. A solar plant has 108 MWp of modules and 90 MWac of inverters. It produces 212,868 MWh in a year of 8,760 hours. What is its capacity factor for the year on the AC rating?
- 22.5%
- 27.0%
- 32.4%
Show answer
B is correct. 212,868 MWh ÷ (90 MW × 8,760 h) = 27.0%. Option A divides by the DC rating of 108 MWp, which gives the capacity factor on the DC rating. Option C multiplies the 27.0% by the DC/AC ratio of 1.2, although the figure is already on the AC rating.
2. Two solar plants stand at the same site and use the same modules. Plant X has a DC/AC ratio of 1.10 and Plant Y a ratio of 1.35. Which statement is most accurate?
- Plant Y has the higher capacity factor on the AC rating.
- Plant X has the higher capacity factor on the AC rating.
- Both plants have the same capacity factor on the AC rating.
Show answer
A is correct. Plant Y has more module capacity behind each megawatt of inverter capacity, so it produces more per MWac, even after the output that its inverters cut off in the sunniest hours. On the DC rating the two plants lie close together, and Plant Y is slightly lower because of that cut-off output.
3. An energy yield assessment gives a specific yield of 1,780 kWh/kWp for a solar plant with a DC/AC ratio of 1.20. What is its capacity factor on the AC rating for a year of 8,760 hours?
- 16.9%
- 20.3%
- 24.4%
Show answer
C is correct. 1,780 h ÷ 8,760 h = 20.3% on the DC rating. Each MWac has 1.20 MWp behind it, so the figure on the AC rating is 20.3% × 1.20 = 24.4%. Option A divides by the ratio instead of multiplying. Option B is the capacity factor on the DC rating.
Free PDF · The RVA Body of Knowledge
The complete curriculum of renewable energy project finance
42 readings in five topic areas, from power and energy to debt sizing and battery storage, with practice questions after every reading. The Complete Edition is free.
Go deeper
- Full load hours and capacity factor: both measures, the conversion between them and a calculator.
- Energy yield: gross yield, net yield and specific yield in kWh/kWp.
- Wind capacity factor: onshore and offshore wind, by market and by month.
- How many homes can 1 MW power? The capacity factor in a calculation that announcements use.
- More articles on energy systems and markets.
- The RVA Certification Program shows how production becomes revenue in a financial model.
Sources: Fraunhofer ISE, Energy-Charts (full load hours in Germany, 2015 to 2025); Department for Energy Security and Net Zero, Digest of UK Energy Statistics 2026 (load factors for 2025); International Renewable Energy Agency, Renewable Power Generation Costs in 2025; Lawrence Berkeley National Laboratory, Utility-Scale Solar, 2026 edition; U.S. Energy Information Administration, Electric Power Annual, data year 2025. Figures checked on November 28, 2026. The plants in the examples are illustrative and come from the RVA Body of Knowledge.
FAQs
What is a good capacity factor for solar?
It depends on the site and on the rating. Published averages are about 11% in Germany and the United Kingdom and 24.0% in the United States on the AC rating. Plants completed worldwide in 2025 average 16.5% on the DC rating (International Renewable Energy Agency). The sunniest regions of the United States average 33% on the AC rating (Berkeley Lab).
Why is the capacity factor of solar lower than that of other power plants?
A solar plant produces only in daylight and reaches its rated power only under strong sun. Nights, clouds, the low sun of the winter months and the hours around sunrise and sunset keep its production below the rated power. The figure measures how much the plant is used. It does not measure its quality.
Is the solar capacity factor calculated on DC or AC capacity?
Both are in use. The International Renewable Energy Agency reports capacity factors on the DC rating of the modules, and the statistics of the United States use the AC rating. The AC figure is higher by the DC/AC ratio of the plant, so state the rating with every solar capacity factor.
How do you convert specific yield in kWh/kWp into a capacity factor?
Divide the specific yield by the 8,760 hours of a year. A specific yield of 1,950 kWh/kWp is a capacity factor of 22.3% on the DC rating. Multiply by the DC/AC ratio to get the figure on the AC rating: 22.3% × 1.25 = 27.8%.
Do trackers increase the solar capacity factor?
Yes. Trackers turn the modules to follow the sun through the day, so the plant produces more in the morning and in the evening. In the United States, plants on trackers reach about five percentage points more than plants with fixed modules, on the AC rating (Berkeley Lab).
What is the difference between the capacity factor and the efficiency of a solar plant?
Efficiency is the share of the sunlight on a module that the module turns into electricity. The capacity factor compares the production of the plant over a period with its production at full rated power in every hour. A plant with highly efficient modules at a cloudy site still has a low capacity factor.